	  Control
      
        -  Open loop vector control
 
        -  Speed or torque control
 
        -  Speed reference input: 0-10V, 0-20mA, 4-20mA, (-10 to +10V SM-I/O 
          Lite option)
 
        -  4 digital inputs- World (enable, run forward, run reverse, local/remote)- 
          USA (not stop, run, jog, local/remote)
 
        -  Switching frequency: 3 (default) – 6 – 12– 18 kHz
 
        -  Output frequency 0 to 1500Hz
 
        -  Accel and Decel ramps (linear and S type)
 
        -  Positive logic control
 
        -  Serial communication - Modbus RTU RS485 via RJ45 connector- Baud 
          rate 4800, 9600, 19200or 38400 bits per second
 
        -  DC injection braking as standard
 
        -  Dynamic braking transistor as standard
 
        -  Dynamic motor flux V/Hz for energy saving
 
        -  Quadratic motor flux V/Hz for fan and pump optimization
 
       
      General Characteristics
      
        -  Maximum overload 150% of rated current for 60s
 
        -  Intelligent Thermal Management (ITM) optimises switching frequency
 
        -  8 preset speeds
 
        -  Flying start
 
        -  Mains dip ride through
 
        -  Automatic no-spin autotune for fast performance optimization
 
        -  Keypad access to all parameters for more demanding set-ups
 
       
      Environment
      
        -  NEMA 1 rating with optional cover
 
        -  Ambient temperature -10 to +40°C @ 3kHz switching
 
        -  Humidity 95% maximum (non-condensing)
 
        -  Electromagnetic Immunity complies with EN61800-3 and EN61000-6-3 and 4
 
        -  Electromagnetic Emissions complies with EN61800-3 (second environment) 
          as standard. Complies with EN61000-6-3 (residential)and EN61000-6-4 
          (industrial) generic standards with optional footprint EMC filter
 
       
      Protection
      Undervoltage, Supply and DC Link overvoltage, Phase loss, Drive overload, 
        Instantaneous overcurrent, Short circuit, Ground fault, Drive thermal, 
        Watchdog, Motor thermal.  |